Apollo Smoke Detector XP95 Bedienungsanleitung Seite 7

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 11
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 6
Document Ref. XP95app.doc/Rev1 09.06.99 Page 7 of 11 Originator MC Checked by AC
5.4.1 Input and Output Response Chart
Part
no.
Description Type
Code
I/P 1 I/P 2 I/P 3 Programmable Output
Channel
BIT 0 BIT 1 Bit 2
A1446 SOUNDER
CONTROL
1 mode 1 mode 2 remote
fault
cont.
prog.
pulsed
prog.
prog. v/f
relay
A1445 I/O UNIT 2 mode 1 mode 2 mode 3 prog prog prog
A1445 ION. SMOKE 3 fire alert data flt rem. lamp dev.test dev.led
A1444/7 ZONE MON. 4 fire valve
closed
rem. flt on reset prog. prog.
A1445 OPTICAL SMOKE 5 fire alert data flt rem. lamp dev. test dev. led
A1445 HEAT DETECTOR 6 fire alert data flt rem. lamp dev. test dev. led
A1445 PRIORITY DEV. 7 fire dev. flt data flt rem. lamp dev. test dev. led
DO NOT
USE
---- 8 ---- ---- ---- ---- ---- ----
A1445/7 MONITOR 1 9 fire A fire B rem. flt prog prog prog
DO NOT
USE
---- 10 ---- ---- ---- ---- ---- ----
DO NOT
USE
---- 11 ---- ---- ---- ---- ---- ----
DO NOT
USE
---- 12 ---- ---- ---- ---- ---- ----
DO NOT
USE
---- 13 ---- ---- ---- ---- ---- ----
DO NOT
USE
---- 14 ---- ---- ---- ---- ---- ----
DO NOT
USE
---- 15 ---- ---- ---- ---- ---- ----
5.5 Notes
5.5.1 The A1444 may be configured for any type code setting and will give the appropriate
input response. No outputs are available.
5.5.2 The A1447 may be used for remote monitoring of either latching or non-latching
inputs.
Use type 4 or type 9. Type 4 automatically generates a reset bit. Type 9 must have the reset
bit programmed.
When used with the A1446, it is not possible to provide a latching/reset facility through the
A1447. Therefore non-latching monitoring only is possible.
5.5.3 Channel A will automatically operate for 10 seconds upon System Reset when the
A1444/A1445 is set to a type 4.
5.6 Outstation Enclosures
The outstations are supplied in steel cabinets as listed in section 2.0.
Seitenansicht 6
1 2 3 4 5 6 7 8 9 10 11

Kommentare zu diesen Handbüchern

Keine Kommentare