Document Ref. XP95app.doc/Rev1 09.06.99 Page 4 of 11 Originator MC Checked by AC
5.0 Outstations
The A1444, A1445, A1446 and A1447 outstations are a series of modules designed to allow
loop input and output functions when used with the Puissant analogue addressable panels.
Each outstation is configured to the required address number and its input/output response by
setting its DIL switch. They are supplied as either boxed or boxed with a power supply and
battery space.
The maximum number of output devices that may be fitted to each loop is determined within
the Puissant panel’s Cause/Effect programming. {Please refer to Programming Guide}
5.1 Outstation Facilities
5.1.1 A1444 Allows remote monitoring of 3 voltage free contacts, either normally open
or normally closed. Inputs are prioritised. Input 1 will override input 2,
input 2 will override input 3. Powered from the detection loop.
5.1.2 A1445 As A1444, except with the addition of 3 independently programmable
output changeover relays (contacts rated 8A @ 30V DC). External
power
supply required (500mA minimum required).
5.1.3 A1446 As A1444, except with the addition of one 2 stage alarm circuit and one
changeover programmable relay (750mA alarm circuit, 1A @ 30V DC
relay contact). External power supply required (1 Amp minimum).
5.1.4 A1447 Will fit to A1444, A1445, A1446 to convert 1 or 2 of the inputs to
monitored detection zones. External power supply required (100mA
minimum).