Document Ref. XP95app.doc/Rev1 09.06.99 Page 6 of 11 Originator MC Checked by AC
5.3 Typical Schematic Drawing for A1446 Outstation
5.4 Input and Output Responses
The following chart lists the input/output responses by type code setting the unit’s DIL
switch.
The columns are as follows:
Part number The most suitable product for the type code setting listed.
Type A description of its type function.
Code The type code number.
Input (IP 1,2,3) The three outstation inputs. The columns describe the text display
response at the control panel.
Mode 1, 2 & 3 indicate on the panel display and sound its internal buzzer
only.
Alert/Valve closed will put the panel into its alert mode with full
display operation but no alarm circuit operation.
Fire will cause the panel to give a normal fire response.
Fault will cause the panel to give a fault display and operate the common
fault relay.
Refer to Programming Guide/Disk for cause/effect programming options..
Programmable Independent programmable outputs. Prog. indicates that the function is
Output Channel programmable by the panel’s cause/effect. The terminology “Channel
A, B, C A,B,C” appears on the PC-based panel cause & effect programme.
All other output responses are pre-set and cannot be changed.
NOTE: Channels A,B,C correspond to the Apollo output bits 0,1,2, respectively.